Appendix C: UL Listed Grade A Control Unit Requirements
56
Table2: Contact ID Zone Alarm/Resto-
ral Event Codes (as per ADEMCO):
Program any of these codes for zone alarms/restorals
when using the standard (non-automatic) Contact ID
reporting format.
Table 3: SIA Format Automatic
Zone Alarm/Restoral Codes
Appendix C: UL Listed Grade A
Control Unit Requirements
Installer should verify communication format
between control unit and receiver.
Entry delay must not exceed 38 seconds.
Exit delay must not exceed 54 seconds.
Minimum bell cutoff time is 4 minutes.
Keyswitch (if used) must be mounted in a pro-
tected area.
‘Quick Exit’ feature must be disabled.
‘Bell Squawk on Trouble’ feature must be enabled.
Minimum ‘Dialing Attempt’ must be 5 and maxi-
mum 10.
Hardwired zones must be EOL configuration.
‘Code Required to Bypass Zones’ must be enabled.
‘Bypass Status not Displayed While Armed’ option
selected.
‘Test Transmission Cycle’ must be set for daily
transmission.
‘Keypad Lockout’ must be programmed.
‘Temporal Three Fire Signal’ must be enabled.
‘Closing Confirmation’ must be enabled.
‘UL Communications Priority’ must be enabled.
‘One time 1-hour User Enabled DLS Window’ must
be enabled.
‘Answering Machine/Double Call’ option must
NOT be enabled.
‘Wireless Supervisory Window’ must be pro-
grammed 4 hours or less.
‘RF Jamming Detection Zone’ must be pro-
grammed; zone type ‘Instant’.
NOTE:This control unit is to be checked by a qualified technician at least once every 3 years.
Medical Alarms (1)34 Entry / Exit
(1)AA Medical (1)35 Day / Night
(1)A1 Pendant Transmitter (1)36 Outdoor
(1)A2 Fail to Report In (1)37 Tamper
Fire Alarms (1)38 Near Alarm
(1)1A Fire Alarm General Alarms
(1)11 Smoke (1)4A General Alarm
(1)12 Combustion (1)43 Exp. module failure
(1)13 Water Flow (1)44 Sensor tamper
(1)14 Heat (1)45 Module Tamper
(1)15 Pull Station (1)4A Cross Zone Police Code
(1)16 Duct 24 Hour Non-Burglary
(1)17 Flame (1)5A 24 Hour non-Burg
(1)18 Near Alarm (1)51 Gas detected
Panic Alarms (1)52 Refrigeration
(1)2A Panic (1)53 Loss of Heat
(1)21 Duress (1)54 Water Leakage
(1)22 Silent (1)55 Foil Break
(1)23 Audible (1)56 Day Trouble
Burglar Alarms (1)57 Low bottled Gas level
(1)3A Burglary (1)58 High Temp
(1)31 Perimeter (1)59 Low Temp
(1)32 Interior (1)61 Loss of Air Flow
(1)33 24 Hour
Zone Definition
SIA Auto Rep
Codes*
Zone Alm/Rest.
Delay, Instant, Interior, Delay
Stay/Away, Interior Stay/Away,
24Hr Burg.
BA-ZZ/BH-ZZ
24Hr Supervisory Buzzer UA-ZZ/UH-ZZ
24Hr Sprinkler SA-ZZ/SH-ZZ
24Hr Gas GA-ZZ/GH-ZZ
24Hr Heat KA-ZZ/KH-ZZ
24Hr Medical MA-ZZ/MH-ZZ
24Hr Emergency (non-medical) QA-ZZ/QH-ZZ
24Hr Waterflow WA-ZZ/WH-ZZ
24Hr Freeze ZA-ZZ/ZH-ZZ
24Hr Holdup HA-ZZ/HH-ZZ
24Hr Panic PA-ZZ/PH-ZZ
Latching 24Hr BA-ZZ/BH-ZZ
* ZZ = zones 01-32